Plixus power calculator

1.                    Introduction

This application note explains how to use the Plixus power calculator

The Plixus power calculator is an important tool to determine :

-          how much units can be connected per branch , depending on type of units , section of cables , length of cables

-          what total max power of the installation will be

-          Detect were potential problems of overcurrent or power loss may occur


2.                    Calculator overview no F/MM

In example below a screenshot of the calculator tool




The calculator tool allows calculation up to 8 NE/NEXT in one branch/loop to the Plixus AE/MME

If more branches of NE/NEXT are used , the calculation must be done for all the Plixus AE/MME branches

3.                    Calculator tool parameters

3.1.            Legend

Each parameter has a specific color , which indicates its function


 

3.2.            Amount of NE/NEXT

Enter the total amount of NE/NEXT in the branch/loop for which you want to enable the calculation

If all devices are connected directly to Plixus AE/MME, without NE/NEXT, then choose 1, then the 4 NE ports represent the 4 Plixus AE/MME ports



3.3.            Cable section of 48V power supply to NE/NEXT

Select the cable section (drop down menu) and cable length from power cable to first NE/NEXT in the branch. And select each cable length to the following NE/NEXT (daisy chain connection)In below example , running power cable is 20 meters and connection from NE 1 to NE 2 is 1 m. power cable has a section of 1.5mm²

 

3.4.            Branch name (optional)      

Each branch name can be edited to enter cabling diagram reference for example

    

3.5.            Start voltage

The calculated voltage at Port 1/2/3/4 of NE/NEXT

    

3.6.            Device type selection

Via drop down menu device type selection can be made ; this will automatically result in another max power indication

Set the amount of units on this branch

If a mix of unit types is used , select the one with highest max power

 


3.7.            Running datacable length and section

Enter the length of the running datacable (cable from NE/NEXT or AE/MME port to first unit in the branch). Select also the used cable section (AWG value) via the drop down menu .

The Ohm/m value will be automatically adapted depending on selected AWG value

    


3.8.            Datacable length and section between units

Enter the average length of the datacable between devices in that branch . Select also the used cable section (AWG value) via the drop down menu .

The Ohm/m value will be automatically adapted depending on selected AWG value

  


3.9.            Calculation

Press the calculate button to check the results



3.9.1.         Result can not be calculated

If a result can not be calculated due to some settings that are very far out of accepatable limits , an  “invalid” message appears for all branches



3.9.2.         Result out can be calculated but result is out of specs

Non allowed end results are marked in red : check what parameters can be changed to obtain a better result (other cable section , less units per branch…)

Max current may not exceed 2A

Voltage at end of line may not be less the 36V



3.9.3.         Results all within allowed limits

No red markings , so results acceptable



3.10.      Total power use for all no F/MM devices

If total power is less then 400 W , internal power supply of Plixsu AE/MME is sufficient

If total power exceeds 400 W , external or additional power supply is needed



If total power exceeds 1000W or max current exceeds 16A , result is marked in red

16 A is max current limit that is allowed on the NE/NEXT power connectors



4.                    Calculator tool F/MM


4.1.            Amount of used power branches

Set amount of power branches and optionally enter branch name

 



4.2.            Device type and amount

Set type of F/MM and amount



4.3.            Running power  cable length and section

Enter length and wiresection of the power cable from power supply to first unit



4.4.            Power cable between units

Enter length and wiresection of the power cable between F/MMs (power connection between F/MMs is done via daisy change




4.5.            Calculate result


4.5.1.         Result can not be calculated

If a result can not be calculated due to some settings that are very far out of accepatable limits , an  “invalid” message appears for all branches



4.5.2.         Result out can be calculated but result is out of specs

 Non allowed end results are marked in red : check what parameters can be changed to obtain a better       

                    result (other cable section , less units per branch…)


 Max current may not exceed 16A

 Voltage at end of line may not be less the 36V



4.5.3.         Results all within allowed limits

No red markings , so results acceptable


 



4.6.            Total power use for all F/MM devices

Total power indication will be marked red if max power exceeds 1000W or max current exceeds 21A



5.                    Total power use for all units

For total power requirement , calculate sum of result in 4.6 and 3.10


Creation date: 11/07/2019 15:20 (b.maertens@televic.com)      Updated: 11/10/2019 10:41 (b.maertens@televic.com)
Files   
DataImage16.png
23.4 KB resend
DataImage16.png
47.3 KB resend
DataImage18.png
96.1 KB resend
DataImage2.png
65.4 KB resend
DataImage2.png
17.1 KB resend
DataImage21.png
49.4 KB resend
DataImage22.png
42.7 KB resend
DataImage30.png
228.2 KB resend
DataImage36.png
56.7 KB resend
DataImage36.png
12.5 KB resend
DataImage37.png
49.9 KB resend
DataImage37.png
63.7 KB resend
DataImage37.png
72.5 KB resend
DataImage41.png
73.3 KB resend
DataImage41.png
128 KB resend
DataImage5.png
99.2 KB resend
DataImage52.png
101.7 KB resend
DataImage55.png
48.3 KB resend
DataImage57.png
47.7 KB resend
DataImage65.png
10.5 KB resend
DataImage71.png
44.9 KB resend
DataImage76.png
97.4 KB resend
DataImage85.png
218 KB resend
DataImage91.png
47.4 KB resend
DataImage91.png
46 KB resend
DataImage92.png
69 KB resend
DataImage96.png
556 KB resend
DataImage99.png
46.1 KB resend
powercalc_plixus_1.09.xlsm
546.3 KB resend